35kV以下液浸式配电变压器:以绝缘液体作为绝缘介质,具有结构简单、运行稳定、可靠性高、运行噪音低、直接联网使用等特点。广泛应用于负载率较低的电力系统:农村乡镇、油田、生活用电。适用于各种电力、特种配电领域。更能适应冲击负荷大、负载波动性较大、负载变化频繁,冲击性负载发生较频繁的场所。

Back
Parameter table
10 kV 三相油浸式配电变压器
额定容量 kVA电压组合及分接范围联结组标号1级2级3级空载电流 %短路阻抗 %
高压 kV低压 kV空载损耗 kw负载损耗 kw空载损耗 kw负载损耗 kw空载损耗 kw负载损耗 kw
306~11±5或±2×2.5%0.4Yyn0 或 Dyn1165455/43070505/48080630/6001.84
5080655/62590730/695100910/8701.6
6390785/745100870/8301101090/10401.5
80105945/9001151050/10001301310/12501.4
1001201140/10801351265/12001501580/15001.3
1251351360/12951501510/14401701890/18001.2
1601601665/15851801850/17602002310/22001.1
2001901970/18702152185/20802402730/26001
2502302300/21952602560/24402903200/30500.9
3152702760/26303053065/29203403830/36500.8
4003303250/30953703615/34404104520/43000.7
5003853900/37104304330/41204805410/51500.7
6304604460510496057062000.64.5
8005605400630600070075000.6
100066574157458240830103000.5
125078086408709600970120000.4
1600940104401050116001170145000.45
20001085131801225146401550183000.4
25001280152701440169601830212000.4

20 kV 三相油浸式配电变压器
额定容量 kVA电压组合及分接范围联结组标号1级2级3级空载电流 %短路阻抗 %
高压 kV低压 kV空载损耗 kw负载损耗 kw空载损耗 kw负载损耗 kw空载损耗 kw负载损耗 kw
3020±5或±2×2.5%0.4Yyn0 或 Dyn1170510855701006002.15.5
5091739.5110.5826.51308702
801191105144.5123517013001.8
1001401275170142520015001.6
1251681530204171024018001.5
1601961870238209028022001.4
2002382210289247034026001.3
2502802635340294540031001.2
3153363145408351548037001.1
4003993740484.5418057044001
5004764505578503568053001
6305675440688.5608081064000.96
8006866545833731598077000.8
10008057820977.58740115092000.7
125094593501147.5104501350110000.7
16001155110501402.5123501650130000.6
20001365131751657.5147251950155000.6
25001610157251955175752300185000.5

35 kV 三相油浸式配电变压器
额定容量 kVA电压组合及分接范围联结组标号1级2级3级空载电流 %短路阻抗 %
高压 kV低压 kV空载损耗 kw负载损耗 kw空载损耗 kw负载损耗 kw空载损耗 kw负载损耗 kw
5035±5或±2×2.5%0.4Yyn0 或 Dyn1176925899251079791.36.5
1001271556150155618016471.1
1251511840178184021319471.1
1601812214214221425623181
2002152618253261830327701
2502543095299309535832750.95
3153023681355368142638940.95
4003614403425440351046580.85
5004275205503520560355070.85
6305086190598619071865500.65
8006087405715740585878350.65
1000719875484687541015115000.65
1250850103491000103491200109500.6
16001022124541203124541444131760.6
20001209147231422147231707155770.55
25001429174051681174052018184150.55

35 kV 油浸式三相双绕组无励磁调压电力变压器
额定容量 kVA电压组合及分接范围联结组标号1级2级3级空载电流 %短路阻抗 %
高压 kV低压 kV空载损耗 kw负载损耗 kw空载损耗 kw负载损耗 kw空载损耗 kw负载损耗 kw
315035~38.5±2×2.5%3.15 6.3 10.5Yd111.720.7220.72.421.90.367
4000224.62.324.62.925.90.36
50002.428.22.828.23.529.70.36
630035~38.5±2×2.5%3.15 3.3 6.3 6.6 10.5YNd112.931.53.431.54.233.30.368
8000434.64.734.65.836.50.28
100004.840.85.740.87430.28
125005.548.46.548.4851.10.24
160006.759.27.959.29.762.50.24
200007.971.69.471.611.575.50.24
250009.484.611.184.613.689.30.2
3150011.1100.813.1100.816.2106.40.210

35 kV 油浸式三相双绕组有载调压电力变压器
额定容量 kVA电压组合及分接范围联结组标号1级2级3级空载电流 %短路阻抗 %
高压 kV低压 kV空载损耗 kw负载损耗 kw空载损耗 kw负载损耗 kw空载损耗 kw负载损耗 kw
315035~38.5±3×2.5%6.3 10.5Yd111.822.22.122.22.623.50.47
40002.126.22.526.23.127.60.4
50002.630.8330.83.732.50.4
630035~38.5±3×2.5%6.3 6.6 10.5YNd113.1333.7334.534.90.47.5
80004.336.55.136.56.338.60.32
100005.143.2643.27.445.60.32
12500651.17.151.18.7540.288
160007.263.38.563.310.566.80.28
200008.574.410.174.412.478.60.28
2500010.18811.98814.692.90.2410
3150012104.414.2104.417.4110.20.24